Pulse output settings to change the configuration, the switches on the inside of the machine door must be switched to the top position Place the read head on the viewport next to the keyboard on the front of the device connect the read head cable to the USB port of the computer in the Device Manager (click Start, type Device Manager in the Search Programs and Files box and open it) check the assigned port number in the COM and LPT Ports section - COM20 in our case Open TELVES In the Measured …
-
Elster gas meter RVG - INS-W11 pulse output connection
For sensing pulses from the RVG rotary gas meter, an INS-W11 6-pin connector is used. The pins on the connector are shown in the following figure: The pulse output is on pins 1 (+) and 2 (-), the pulse value is 10 pulses / m3 for G10-G65, 1 pulse / m3 for G100-G250.
-
Setting up the Schneider Electric iEM3000 Series Meter
The iEM3000 series meters provide a large amount of information on basic MBus, including streams and power in each phase. Enter settings To enter the settings, press and hold the OK and ESC buttons for a few seconds. The factory password is 0010. Scroll to each digit with the arrow key and confirm with OK. Setting the gear ratio of the measuring transformers Use the arrow button to scroll to CT&VT Ratio, press OK to set.
-
Connecting the Gioanola water meter pulse output
Cold and hot water meters from the Italian manufacturer Gioanola use their own system of pulse outputs. The read head with a reed contact always senses a dial that is markedly marked and different from the others. Therefore, if, as in the following figure, a target measuring one thousandth of m3 (0.001 m3) is measured, the weight of one pulse is one hundredth of m3 (0.01 m3).
-
Connecting the pulse outputs of the Actaris DC3 meter
The most common wiring of the Actaris DC3 meter outputs is described below. The specific wiring must always be verified with the manufacturer according to the meter number. The common negative pole for all outputs is brought out at terminal 40. The active load is most often connected to terminal 41. Output description Clamp Typical wiring 40 Common pole 41 Active consumption 42 Active delivery 43 Idle subscription 44 Slow delivery
-
Proline Prosonic Flow Meter 90
Depending on the version, the flowmeter can be equipped with a pulse output to monitor the flow rate. The pulse output (only versions with A and D at the end) is output to terminals 24 (+) and 25 (-) marked f-OUT or PULSE/FREQUENCY OUTPUT. Settings are made via the flowmeter display unit Press the E button to enter the settings Use the + and - buttons to find the PULSE/FREQ item.
-
Connecting the pulse outputs of the Itron SL7000
The standard layout of the SL7000 meter input and output terminals for connection of the galvanic isolator in the network of Českomoravská Distribuce (Unicapital Distribuce) is described below. Description of outputs Clamp Functions Typical wiring 29 IV 1 Active consumption 30 IV 2 Active delivery 31 IV 3 Q1 total energy 32 IV 4 Q2 total energy 33 IV 5 Q3 total energy 34 IV 6 Q4 total energy 35 Common pole Description of inputs Clamp Functions Typical wiring 20 ŘV 1 End of the integration period …
-
Connect SmartComs with Inepro Metering PRO380-Mb
In order to begin making the settings, we need to have the following elements: Necessary resources SmartCom PRO ETH with all its cables and connectors. An Inepro Metering PRO380-Mb. An electric cable with the one that appears in the image. Two screwdrivers, one of star and another plane, small. Settings To start the SmartCom must be configured as in this manual: How to connect SmartComs to the Enectiva server?. Connect the longer connector with the power cord, look at the color pattern as it …