Connecting the Gioanola water meter pulse output
Cold and hot water meters from the Italian manufacturer Gioanola use their own system of pulse outputs. The read head with a reed contact always senses a dial that is markedly marked and different from the others. Therefore, if, as in the following figure, a target measuring one thousandth of m3 (0.001 m3) is measured, the weight of one pulse is one hundredth of m3 (0.01 m3).
-
Zenner EDC communication module
Setup of the Zenner EDC module is done over the M-Bus using the Global Meter Manager configuration tool, which can be downloaded from the manufacturer’s website. The manual is available as a pdf file in the “downloads” section on the right side of the screen.
-
Proline Prosonic Flow Meter 90
Depending on the version, the flowmeter can be equipped with a pulse output to monitor the flow rate. The pulse output (only versions with A and D at the end) is output to terminals 24 (+) and 25 (-) marked f-OUT or PULSE/FREQUENCY OUTPUT. Settings are made via the flowmeter display unit Press the E button to enter the settings Use the + and - buttons to find the PULSE/FREQ item.
-
Pulse module Elster PR6 / PR7
The PR6 and PR7 pulse modules are used for reading Elster water meters. The PR6 sensor is designed for domestic water meters R ½" - 2" type V200, V200P, V220, C4000 (small water meter marked V220) Sensor PR7 is designed for industrial water meters DN 40 - DN 300 , type H4000, H4200, S2000, C4000 ( main counter ), C3100 (main counter since 2008) Installation of PR6 modules PR6 - V200 Tear off the foil Remove the counter cap, attach the PR6 to the cap pin Push the PR6 downward until it …