For sensing pulses from the RVG rotary gas meter, an INS-W11 6-pin connector is used.
The pins on the connector are shown in the following figure:
The pulse output is on pins 1 (+) and 2 (-),
the pulse value is 10 pulses / m3 for G10-G65, 1 pulse / m3 for G100-G250.