Pulse output settings

  • to change the configuration, the switches on the inside of the machine door must be switched to the top position

  • Place the read head on the viewport next to the keyboard on the front of the device

  • connect the read head cable to the USB port of the computer
  • in the Device Manager (click Start, type Device Manager in the Search Programs and Files box and open it) check the assigned port number in the COM and LPT Ports section - COM20 in our case

  • Open TELVES
  • In the Measured Telemetry Points window:
    • in the View section, select Communication (1)
    • under the Communication channel name field, select the communication port number detected in the device manager (eg COM20) (2)
    • Click Read (3) in the top menu and select Parameters

  • In the object tree on the left of the window
    • first click on the Hardware item (1) with the left mouse button to mark it
    • right-click Hardware to select options
    • Hover over the Add output variable item and click Impulse Quantity in the newly displayed menu
    • Click the Create New Equation button in the right part of the window

  • in the Math Expression Assistant, select the following options one at a time. Click the desired value and then click Continue

  • Click Save to Device at the bottom of the window. After successful registration the program informs us with the message “Parameters have been written”