Pulse output settings
- to change the configuration, the switches on the inside of the machine door must be switched to the top position
- Place the read head on the viewport next to the keyboard on the front of the device
- connect the read head cable to the USB port of the computer
- in the Device Manager (click Start, type Device Manager in the Search Programs and Files box and open it) check the assigned port number in the COM and LPT Ports section - COM20 in our case
- Open TELVES
- In the Measured Telemetry Points window:
- in the View section, select Communication (1)
- under the Communication channel name field, select the communication port number detected in the device manager (eg COM20) (2)
- Click Read (3) in the top menu and select Parameters
- In the object tree on the left of the window
- first click on the Hardware item (1) with the left mouse button to mark it
- right-click Hardware to select options
- Hover over the Add output variable item and click Impulse Quantity in the newly displayed menu
- Click the Create New Equation button in the right part of the window
- in the Math Expression Assistant, select the following options one at a time. Click the desired value and then click Continue
- Click Save to Device at the bottom of the window. After successful registration the program informs us with the message “Parameters have been written”